組合式空氣處理機組是提供(gong)新(xin)(xin)鮮空(kong)(kong)氣(qi)(qi)的一種空(kong)(kong)氣(qi)(qi)調節設備。功(gong)能(neng)上(shang)按使(shi)用(yong)環(huan)境(jing)的要求(qiu)可以達到(dao)恒(heng)溫(wen)(wen)恒(heng)濕(shi)或者(zhe)單純提供(gong)新(xin)(xin)鮮空(kong)(kong)氣(qi)(qi)。工作原理(li)是在室(shi)外(wai)抽取新(xin)(xin)鮮的空(kong)(kong)氣(qi)(qi)經過(guo)除(chu)塵(chen)、除(chu)濕(shi)(或加濕(shi))、降溫(wen)(wen)(或升溫(wen)(wen))等處理(li)后通過(guo)風機送到(dao)室(shi)內(nei),在進入室(shi)內(nei)空(kong)(kong)間時替換室(shi)內(nei)原有(you)的空(kong)(kong)氣(qi)(qi)。當然以上(shang)所提到(dao)的功(gong)能(neng)得根據使(shi)用(yong)環(huan)境(jing)的需求(qiu)來定(ding),功(gong)能(neng)越(yue)齊(qi)全造價越(yue)高。



組合式空氣處理機組日常維護


組合式空氣處理機組故障


組(zu)(zu)合(he)(he)式(shi)(shi)空(kong)氣(qi)處理(li)機組(zu)(zu)的(de)(de)故障主要(yao)是換熱器被凍(dong)(dong)裂,某大廈(sha)采用(yong)冷水機組(zu)(zu)VAV空(kong)調系統,從施工到調試再到投人運行共出(chu)現(xian)了4起(qi)組(zu)(zu)合(he)(he)式(shi)(shi)空(kong)氣(qi)處理(li)機組(zu)(zu)凍(dong)(dong)裂事故,該大廈(sha)組(zu)(zu)合(he)(he)式(shi)(shi)空(kong)氣(qi)處理(li)機組(zu)(zu)總(zong)共15臺(tai),凍(dong)(dong)裂的(de)(de)比例高達27%。究其原因,主要(yao)有以下4個方(fang)面。


a)臨(lin)時管(guan)線未經沖洗即對組合式空氣處理機(ji)組供水


為了趕工期經常用(yong)(yong)(yong)組(zu)(zu)合(he)式(shi)(shi)空氣(qi)(qi)處理機組(zu)(zu)進行臨(lin)時供暖,但由于時間緊迫整個供暖系統未(wei)正(zheng)式(shi)(shi)用(yong)(yong)(yong)水(shui)(shui)(shui)沖洗,供回(hui)水(shui)(shui)(shui)管道全(quan)部(bu)采用(yong)(yong)(yong)主管下接支管的(de)連(lian)接方式(shi)(shi),結果管線內(nei)污物在距(ju)換熱站(zhan)較近的(de)組(zu)(zu)合(he)式(shi)(shi)空氣(qi)(qi)處理機組(zu)(zu)加熱器內(nei)不(bu)斷淤積(ji),熱水(shui)(shui)(shui)流(liu)量不(bu)斷減少,從而導致(zhi)加熱器凍(dong)裂。從本質上來(lai)講(jiang),臨(lin)時供水(shui)(shui)(shui)管線施工時未(wei)按(an)施工規程進行沖洗而盲目(mu)投入使用(yong)(yong)(yong)造成了加熱器的(de)凍(dong)裂。


b)自控(kong)閥門指示的閥位有(you)誤


集(ji)中(zhong)空調自控系(xi)統(tong)(tong)的(de)(de)施工往往滯后(hou),常常在(zai)(zai)(zai)大(da)廈(sha)正式投(tou)人使用后(hou)才開(kai)始調試(shi)(shi)弱電系(xi)統(tong)(tong)。在(zai)(zai)(zai)自控系(xi)統(tong)(tong)啟(qi)用之前(qian)組(zu)合式空氣處(chu)理機組(zu)能夠正常運行,啟(qi)用后(hou)反(fan)而發(fa)生了凍裂事(shi)(shi)故(gu)。該事(shi)(shi)故(gu)發(fa)生在(zai)(zai)(zai)冬季空調自控系(xi)統(tong)(tong)安(an)裝(zhuang)調試(shi)(shi)過程中(zhong),安(an)裝(zhuang)誤操作使組(zu)合式空氣處(chu)理機組(zu)的(de)(de)水(shui)閥開(kai)閉指示(shi)位置(zhi)與自控系(xi)統(tong)(tong)的(de)(de)電腦(nao)指示(shi)正好相反(fan),組(zu)合式空氣處(chu)理機組(zu)供水(shui)實際是自控系(xi)統(tong)(tong)指示(shi)的(de)(de)斷流狀(zhuang)態,從而引發(fa)事(shi)(shi)故(gu)。因此(ci)當室外氣溫降至0℃以下(xia)時,應盡(jin)量保持(chi)空調系(xi)統(tong)(tong)穩定運行,水(shui)系(xi)統(tong)(tong)的(de)(de)自控安(an)裝(zhuang)和(he)調試(shi)(shi)應安(an)排在(zai)(zai)(zai)其他季節進行,避(bi)免因調試(shi)(shi)差(cha)錯(cuo)引發(fa)事(shi)(shi)故(gu)。


c)組合式空氣處(chu)理機組冬(dong)季停用時表冷器中有存水